The air conditioner should have a real capacity of 21000 BTU per hour.
Selection of a AC unit for a meeting room
First, we calculate we must calculate the ideal room area ([tex]A[/tex]), in square feet, represented by the following formula:
[tex]A = l\cdot w[/tex] (1)
Where:
- [tex]l[/tex] - Length, in feet.
- [tex]w[/tex] - Width, in feet.
([tex]l = 35\,ft[/tex], [tex]w = 20\,ft[/tex])
[tex]A = (35\,ft)\cdot (20\,ft)[/tex]
[tex]A = 700\,ft^{2}[/tex]
Now we estimate the recommended ideal air conditioner capacity ([tex]C[/tex]), in BTU per hour, by energy charts. According to this source, we have the following recommended ideal capacity:
[tex]A = 700\,ft^{2} \to C = 18000\,\frac{BTU}{h}[/tex]
As ceiling ([tex]h[/tex]), in feet, is greater than 8 feet, we need to add 1000 BTU per hour per each additional foot to the recommended ideal air conditioner capacity. Then, the recommended real air conditioner capacity ([tex]C'[/tex]), in BTU per hour, is:
[tex]C' = C + 1000\cdot (h-h_{min})[/tex], for [tex]h \ge h_{min}[/tex] (2)
Where:
- [tex]C[/tex] - Recommended ideal air conditioner capacity, in BTU per hour.
- [tex]h_{min}[/tex] - Minimum ceiling, in feet.
- [tex]h[/tex] - Current ceiling, in feet.
([tex]C = 18000\,\frac{BTU}{h}[/tex], [tex]h_{min} = 8\,ft[/tex], [tex]h = 11\,ft[/tex])
[tex]C' = 18000\,\frac{BTU}{hr} + 1000\cdot (11\,ft-8\,ft)[/tex]
[tex]C' = 21000\,\frac{BTU}{hr}[/tex]
The air conditioner should have a real capacity of 21000 BTU per hour. [tex]\blacksquare[/tex]