Answer:
a) 0.0338 kg/s
b) 7.04 KW
c) 4.4
d) 0.74 kW
Explanation:
The mass flow rate of the refrigerant is calculated from the energy balance of the water and the refrigerant. The enthalpy values are taken from table A-11
Q_w = Q_r
m_w*c_p*ΔT_w = m_r(h_2-h_1)
m_r = m_w*c_p*ΔT_w/h_2 - (h_liq,12 + qh_evap,12)
= 0.065*4.18*20K/(257.33 - (68.17+0.15*189.16))kJ/kg
= 0.0338 kg/s
The rate of heat supply is calculated from the rejected heat and the work:
Q_h = Q_L + W
= m_r(h_2-h_1)+W
= 7.04 KW
The COP is calculated from the heat supply and work:
COP = Q_h/W
= 4.4
The minimum power is determined from the maximum COP:
W_min = Q_h/COP_max
= Q_h/1/1-T_L/T_H
= 0.74 kW