A 10 kW cooling load is to be served by operating an ideal vapor-compression refrigeration cycle with its evaporator at 400 kPa and its condenser at 800 kPa. Calculate the refrigerant mass flow rate and the compressor power requirement when refrigerant-134a is used. (Take the required values from the saturated refrigerant-134a tables.)

Respuesta :

Answer:

[tex]\dot m = 0.062456 kg/sec[/tex]

b) w = 0.927211 kW

Explanation:

from table R-134 a

state 1  

P-1 = 400 kPa

h_1 = hg@400 kpa = 255.55 kJ?kg

s1 = s2 = 0.92961 kJ/kg K

state 2

P-2 = 800 kPa

s2 =s1 = 0.92691

s2> sg@ 800 kPa = 0.92691 kJ/ kg K

from superheated table for R-134 a at pressure of 800 kPa

using interpolation for obtaining desire value of temperature and enthalapy

[tex]\frac{T_2 - 31.31}{40 - 31.31} = \frac{0.9306 - 09183}{0.9480 - 0.9183}[/tex]

T_2 = 34.75 degree C

FOR  ENTHALAPY

[tex]\frac{h_2 - 267.29}{276.45 - 267.29} = \frac{0.92691 - 0.9183}{0.9480 - 0.9183}[/tex]

h_2 = 270.3928 kJ/kg

state 3

[tex]P_3 = 800 kPA[/tex]

[tex]H_3 = Hf@800 kPa = 95.47 kJ/kg[/tex]

state 4  ( h remain constant)

[tex]h_4 =h_3 = 95.47 kJ/kg[/tex]

a) mass flow rate [tex]\dot m = \frac{cooling head}{\phi _{in}}[/tex]

[tex]\dot m = \frac{10 kW}{255.55 - 95.47}[/tex]

[tex]\dot m = 0.062456 kg/sec[/tex]

b) compressor power [tex]w = \dot m [h_2 -h_1][/tex]

w = 0.062456(270.3928 - 255.55)

w = 0.927211 kW

ACCESS MORE