Scenario 307.1A 600-amp, 120/240-volt, 3Ø, 4-wire service is to be installed in two conduits. The service-entrance conductors installed are 350 kcmil. The two threaded RMC conduits enter the bottom of the CT can where a hole saw was used to cut the holes. The hole saw "walked" a bit and wallowed out the holes so that now you will have to install bonding bushings on the conduits.Refer to Scenario 307.1. The smallest bonding jumper you can install from the ground bar to the bushings is ___ AWG. Only one BJ will be run to hit both bushings. Select one: a.2/0 b.1/0 c.3/0 d.2 e.1